Description

Maintenance switch, 3-p. 415V AC23 80A, 45kW. Mounted auxiliary contact: 0NO0NC. Aluminium enclosure. IP65. Black Round handle. Interlocked cover. The dye casted aluminum alloy (silumin) enclosure is extremely rigid, and well suited for harsh environment. The surface is polyester coated and well protected from corrosion. Installation is made easy, thanks to the easy access to terminals, screwed cover and with the grommet type of glands included (IP54). The cover is interlocked, and handle padlockable with two padlocks. The handle can also be padlocked in On position, by removing two small plastic bits. N and PE terminals included.

Additional information

Weight1.88 kg
Dimensions11.8 × 16 × 23 cm
Extended Product Type

KSE380GTPN-B

Standard

IEC 60947-3

Number of Poles

3P

Rated Current

80A

Rated Voltage

690V

Material

Aluminium

Color

black

Degree of Protection IP

IP65

Rated Cross-Section

1.5…3.5 cm²

Terminal Type

Screw Terminals

Product Net Depth (MM)

11.8 cm

Customs Tariff Number

85363030

Minimum Order Quantity

76

GTIN (EAN)

6.41702E+12

Resistance

Housing IK08

L1

L2

Enclosures & Cabinets

L3

IP66, IP67+), Weatherproof Boxes (IP65

Cable Entry Position

Top and/or Bottom

Cable Outlets Per Side

2xM40 / 2xM40+M16

Country of Origin

Bulgaria

Handle Type

Round

Maximum Mounted Auxiliary Contacts

1 NO, 1 NC

Mechanical Durability

200000

Mounted Auxiliary Contacts

0 NO, 0 NC

Neutral Type

Fixed Neutral

Number of Auxiliary Contacts NC

0

Number of Auxiliary Contacts NO

0

Package Level 1 Depth / Length

17 cm

Package Level 1 Gross Weight

2.06 kg

Package Level 1 Height

24 cm

Package Level 1 Width

15 cm

Pollution Degree

3

Position of Line Terminals

Top In – Bottom Out

Power Loss

at Rated Operating Conditions per Pole 3.4 W

Rated Conditional Short-Circuit Current (Inc)

(415 V AC) 50 kA

Rated Impulse Withstand Voltage (Uimp)

acc. to IEC 60947-2 8 kV

Rated Insulation Voltage (Ui)

acc. to IEC 60947-1 800 V

Rated Operational Current AC-22A (Ie)

(380 … 415 V) 80 A

Rated Operational Current AC-23A (Ie)

(380 … 415 V) 80 A

Rated Operational Power AC-23A (Pe)

(380 … 415 V) 45 A

Rated Short-Circuit Making Capacity (Icm)

(690 V AC) 3.5 kA

Rated Short-time Withstand Current Low Voltage (Icw)

for 1 s 1.5 kA

Special Functions

EMC

Switches Operating Mechanism

On the Front of the Switch

Tightening Torque

acc. IEC 60947-1 2

Wire Stripping Length

Main Circuit 18