Surge protection in UAE panels is no longer optional — DEWA, ADDC, and most main-contractor specifications now require IEC 61643-rated SPDs at every distribution level. Heres how to lay them out and what part numbers to use.
The three SPD types
- Type 1: Lightning current arrester. Installed at the building main incomer (typically near the LV transformer / main MCCB). Rated by impulse current Iimp (kA, 10/350 µs waveform). Common values: 12.5 kA, 25 kA per pole. Required where direct-strike risk exists.
- Type 2: Surge arrester. Installed at sub-distribution boards. Rated by nominal discharge current In and max discharge current Imax (8/20 µs). Common values: In=20 kA, Imax=40-80 kA.
- Type 3: Point-of-use protection. Installed at sensitive equipment (PLCs, CCTV, instrumentation). Rated by combined impulse Uoc (typically 6 kV).
Where each goes in the panel hierarchy
| Panel level | SPD type | Typical Brand Codes |
|---|---|---|
| Main LV switchboard | Type 1+2 (combined) | ABB OVR T1+T2 series, Schneider iPRD1, Phoenix Contact FLASHTRAB |
| Sub-distribution / floor panel | Type 2 | ABB OVR T2, Schneider iPRD, Phoenix Contact VAL-MS |
| Final circuit / control panel | Type 3 or Type 2+3 | Schneider iPRC, Phoenix Contact PLUGTRAB |
Common mistakes
- Installing only Type 2 at the incomer where a Type 1 is required — Type 2 alone will be destroyed by a real lightning strike.
- Forgetting the upstream MCB/fuse — every SPD needs a backup overcurrent device, typically gG fuse 63A or 125A depending on rating.
- Wire length too long — the SPD lead length from busbar to earth should be < 50 cm. Each extra metre adds significant residual voltage.
- Missing remote indication — most SPDs have an NC contact that should be wired back to the BMS so blown cartridges get replaced before the next strike.