ABB

CONTACTOR UA16-30-10RA 240V 50/60Hz

$40.57

UA16-30-10RA 230-240V 50Hz / 240-260V 60Hz Contactor

In Stock

Bulk Pricing

QuantityPrice
1 - 5 $40.57
6 - 10 $39.76
11 - 50 $38.95
51 - 200 $38.14
200+ $37.32

In stock

SKU: 1SBL181024R8810 Category: Tags: , , Brands:
  • ✅ Free global shipping on all orders
  • ✅ 30 days easy returns if you change your mind
  • ✅ Order before noon for same day dispatch
Guaranteed Safe Checkout

Description

The UA16-30-10RA 230-240V 50Hz / 240-260V 60Hz is a 3-pole contactors for capacitor switching, can be used in installations in which the peak current far exceeds 100 times nominal rms current. The contactors are delivered complete with their damping resistors and must be used without additional inductances (see table below). The capacitors must be discharged (maximum residual voltage at terminals ≤ 50 V) before being re-energized when the contactors are making. Their electrical durability is 250 000 operating cycles for Ue < 500 V and 100 000 operating cycles for 500 V ≤ Ue ≤ 690 V. The UA..RA contactors are fitted with a special front mounted block, which ensures the serial insertion of 3 damping resistors into the circuit to limit the current peak on energization of the capacitor bank. Their connection also ensures capacitor precharging in order to limit the second current peak occurring upon making of the main poles. The insertion of resistors allows to damp the highest current peak of the capacitor when switching on, whatever its level. The UA..RA series 3-pole contactors are of the block type design. - Main poles and auxiliary contacts: 3 main poles, 1 built-in auxiliary contact - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.

Additional information

Weight460 g
Dimensions10.7 × 4.4 × 12 cm
Extended Product Type

UA16-30-10RA 230-240V 50Hz / 240-260V 60Hz

Standard

IEC/EN 60947-1, IEC/EN 60947-4-1

Number of Poles

3P

Rated Current

16A

Rated Voltage

690V

Rated Frequency

50/60Hz

Breaking Capacity

100A

Mounting

TH35-15 (35 x 1.5 cm Mounting Rail) acc. to IEC 60715

Degree of Protection IP

IP20

Mounting Type

TH35-15 (35 x 1.5 cm Mounting Rail) acc. to IEC 60715

Rated Cross-Section

0.75…2.5 mm²

Terminal Type

Screw Terminals

Product Net Depth (MM)

10.7 cm

Customs Tariff Number

85364900

Minimum Order Quantity

1

Temperature Range

-60…+80°C

GTIN (EAN)

3.47152E+12

L1

L2

Switchgear & Contactors

L3

Contactors

Climatic Withstand

according to IEC 60068-2-30 and 60068-2-11 – UTE C 63-100 Specification II

Coil Consumption

Average Holding Value 50 / 60 Hz 8 V·A

Connecting Capacity Auxiliary Circuit

Flexible with Cable End 1/2x 0.75 … 2.5 mm²

Connecting Capacity Main Circuit UL/CSA

1x 18-10 AWG

Connecting Terminals (delivered in open position) Main Poles

M 3.5 (+, -) pozidriv 2 screws with cable clamp

Electrical Durability

Ue =< 440 V 250000 cycle

Maximum Electrical Switching Frequency

240 cycles per hour

Maximum Operating Altitude Permissible

Without Derating 3000 m

Minimum Switching Capacity

17 / 5 VLT4K

Mounting by Screws (not supplied)

2 x M4 Screws Placed Diagonally

Number of Auxiliary Contacts NC

0

Number of Auxiliary Contacts NO

1

Number of Main Contacts NC

0

Number of Main Contacts NO

3

Operate Time

Between Coil De-energization and NO Contact Opening 4 … 11 ms

Package Level 1 Depth / Length

15.5 cm

Package Level 1 Gross Weight

460 g

Package Level 1 Height

6.3 cm

Package Level 1 Width

13.5 cm

Pollution Degree

3

Power Loss

at Rated Operating Conditions per Pole 0.1 W

Product Name

Block Contactor

Rated Control Circuit Voltage (Uc)

50 Hz 230 … 240 V

Rated Impulse Withstand Voltage (Uimp)

8 kV

Rated Insulation Voltage (Ui)

acc. to IEC 60947-4-1 1000 V

Rated Operational Current AC-15 (Ie)

(500 V) 2 A

Rated Operational Current DC-13 (Ie)

(24 V) 6 A / 144 W

Rated Operational Power AC-6b (Pe)

(230 / 240 V) 40 °C, 50 / 60 Hz 8 kvar

Rated Short-time Withstand Current Low Voltage (Icw)

for 0.1 s 140 A

Short-Circuit Protective Devices

Auxiliary Circuit – gG Type Fuses 10 A

Tightening Torque

Auxiliary Circuit 1 N·m

Tightening Torque UL/CSA

Auxiliary Circuit 9 in·lb