ABB

OT125F4N2 SWITCH-DISCONNECTOR

$73.52

OT125F4N2 SWITCH-DISCONNECTOR

In Stock

Bulk Pricing

QuantityPrice
1 - 5 $73.52
6 - 10 $72.05
11 - 50 $70.58
51 - 200 $69.11
200+ $67.64

In stock

SKU: 1SCA105051R1001 Category: Tags: , , Brands:
  • ✅ Free global shipping on all orders
  • ✅ 30 days easy returns if you change your mind
  • ✅ Order before noon for same day dispatch
Guaranteed Safe Checkout

Description

4-pole, front operated, base mounted, DIN-rail mountable switch-diconnector / non-fusible diconnect switch with front protected clamp terminals, handle and shaft are not included

Additional information

Weight490 g
Dimensions7.4 × 9.65 × 10 cm
Extended Product Type

OT125F4N2

Standard

IEC 60947-3

Number of Poles

4P

Rated Current

100A

Rated Voltage

750V

Color

grey

Mounting

Base mounting

Row Spacing

Standard

Degree of Protection IP

IP20

Mounting Type

Base mounting

Rated Cross-Section

10…7 cm²

Terminal Type

Screw Terminals

Product Net Depth (MM)

7.4 cm

Customs Tariff Number

85365080

Minimum Order Quantity

10

Operating mode

Front

GTIN (EAN)

6.41702E+12

L1

L2

Switchgear & Contactors

L3

Disconnect Switches

Country of Origin

Finland

Fourth Pole Position

Right Side

Fourth Pole Type

Switched – Simultaneous Function

Handle Type

Knob

Horsepower Rating UL/CSA

(acc. to UL 200 V) 25 Hp

Maximum Operating Voltage UL/CSA

600 V

Mechanical Durability

20000

Package Level 1 Depth / Length

11.2 cm

Package Level 1 Gross Weight

520 g

Package Level 1 Height

10.9 cm

Package Level 1 Width

8.6 cm

Pollution Degree

3

Position of Line Terminals

Top In – Bottom Out

Power Loss

at Rated Operating Conditions per Pole 6.3 W

Rated Conditional Short-Circuit Current (Inc)

(125 A fuse, 415 V) 50 kA

Rated Impulse Withstand Voltage (Uimp)

8 kV

Rated Insulation Voltage (Ui)

acc. to IEC/EN 60664-1 750 V

Rated Operational Current AC-21A (Ie)

(380 … 415 V) 125 A

Rated Operational Current AC-22A (Ie)

(380 … 415 V) 125 A

Rated Operational Current AC-23A (Ie)

(380 … 415 V) 90 A

Rated Operational Power AC-23A (Pe)

(220 … 240 V) 22 kW

Rated Short-Circuit Making Capacity (Icm)

(690 V) 3.6 kA

Rated Short-time Withstand Current Low Voltage (Icw)

for 1 s 2.5 kA

Special Functions

No

Switches Operating Mechanism

Mechanism on Top of the Switch

Tightening Torque

acc. IEC 60947-1 6 N·m

Wire Stripping Length

Main Circuit 18-2.1 cm