F202 A-40/0.03 2CSF202101R1400 Residual Current Devices (RCD)

421.00 AED

Residual Current Circuit Breaker F200 – 2P – 30 mA – 40 A – Type A

On Order

Bulk Pricing

QuantityPrice
1 - 5 421.00 AED
6 - 10 412.58 AED
11 - 50 404.16 AED
51 - 200 395.74 AED
200+ 387.32 AED

Out of stock

  • โœ… Free global shipping on all orders
  • โœ… 30 days easy returns if you change your mind
  • โœ… Order before noon for same day dispatch
Guaranteed Safe Checkout

Description

The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications.

Additional information

Weight200 g
Dimensions6.9 × 3.5 × 8.5 cm
Extended Product Type

F202 A-40/0.03

Standard

IEC/EN 61008

Number of Poles

2P

Rated Current

40A

Rated Voltage

230V

Rated Frequency

60Hz

Rated Residual Current

30mA

Color

Similar to RAL 7035

Mounting

DIN-Rail

Degree of Protection IP

IP20

Tripping Characteristic

Instantaneous

Mounting Type

DIN-Rail

Rated Cross-Section

0โ€ฆ0.25 mmยฒ

Terminal Type

Screw Terminals

Product Net Depth (MM)

6.9 cm

Minimum Order Quantity

1

Temperature Range

-25โ€ฆ55ยฐC

DIN Place Units

2

GTIN (EAN)

8012542782605

Resistance

20 Cycles with Load 0.8 In: 1 g or 0.1 mm 5โ€ฆ150โ€ฆ5 Hz

ABB EcoSolutions

Yes

ABB Site Meeting Group Waste To Landfill Target

No non-hazardous waste is sent to a landfill

Accessories Available

Yes

Accessory Type

Auxiliary contact

Electrical Endurance

10000 cycle

Extended Product Lifetime

Product Durability

Input Voltage Type

AC

Leakage Current Type

A

Maximum Operating Voltage UL/CSA

277 V AC

Mechanical Endurance

20000 cycle

Number of Modules

2

Offered with Takeback Services

Take Back for Recycling

Options Provided

None

Package Level 1 Gross Weight

235 g

Pollution Degree

2

Power Loss

Total 4.8 W

Power Supply Connection

Arbitrary

Rated Conditional Short-Circuit Current (Inc)

10 kA

Rated Impulse Withstand Voltage (Uimp)

4 kV

Rated Insulation Voltage (Ui)

500 V

Recyclability Rate of the Product acc. to EN45555

Design for Closing Resource Loops โ€“ Standard EN45555 โ€“ 82.05 %

Sustainable Material Content in Packaging (wt. %)

Recycled Paper โ€“ 0 %

Test Voltage (Ut)

170-254 V

Tightening Torque

2.8 Nยทm

Type of Residual Current

Type A

Wire Stripping Length

1.2 cm