Additional information
| Weight | 265 g |
|---|---|
| Extended Product Type | MS132-2.5T |
| Standard | IEC/EN 60947-1 |
| Number of Poles | 3P |
| Rated Current | 2.5A |
| Rated Voltage | 690VAC |
| Rated Frequency | 50Hz |
| Breaking Capacity | 100kA |
| Mounting | 1 … 6 |
| Row Spacing | Electrical Conductive Board, Vertical 7.5 cm |
| Degree of Protection IP | IP20 |
| Tripping Characteristic | 1SAM300535F0007 |
| Mounting Type | TH35-15 (35 x 1.5 cm Mounting Rail) acc. to IEC 60715 |
| Rated Cross-Section | 0.75…2.5 mm² |
| Setting range | 1.6…2.5A |
| Terminal type | Screw Terminals |
| Product Net Depth (MM) | 8.675 cm |
| Customs Tariff Number | 85362010 |
| Minimum Order Quantity | 1 |
| Temperature Range | 0…+40°C |
| GTIN (EAN) | 4.01361E+12 |
| Status indicator | ON / OFF / TRIP |
| resistance | 5 g 3 … 150 Hz |
| L1 | Electrical |
| L2 | Power Distribution |
| L3 | Fuses & Fuse Holders |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| Actuator Type | Rotary Handle |
| Ambient Air Temperature Compensation | Yes |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1/2x 16-12 AWG |
| Country of Origin | Germany |
| Criticality | No |
| Electrical Durability | 50000 cycle |
| Full Load Amps Motor Use | (120 V AC) Single Phase 2.5 A |
| Horsepower Rating UL/CSA | (220 … 240 V AC) Single Phase 0.17 Hp |
| Locked Rotor Amps | (120 V AC) Single Phase 15 A |
| Maximum Operating Altitude Permissible | 2000 m |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Mechanical Durability | Nr. Operations 100000 cycle |
| Note | No |
| Package Level 1 Depth / Length | 9.5 cm |
| Package Level 1 Gross Weight | 280 g |
| Package Level 1 Height | 5 cm |
| Package Level 1 Width | 9.2 cm |
| Package Level 2 Depth / Length | 39.5 cm |
| Package Level 2 Gross Weight | 11.586 kg |
| Package Level 2 Height | 21 cm |
| Package Level 2 Units | carton 40 piece |
| Package Level 2 Width | 28 cm |
| Pollution Degree | 3 |
| Power Loss | at Rated Operating Conditions per Pole 0.6 … 1.6 W |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 50 A |
| Rated Insulation Voltage (Ui) | 690 V |
| Recommended Screw Driver | M3.5 |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops – Standard EN45555 – 80 % |
| Tightening Torque | Main Circuit 0.8 … 1.2 N·m |
| Tightening Torque UL/CSA | Main Circuit 10 … 12 in·lb |
| Wire Stripping Length | Main Circuit 9 mm |