| Weight | 14 kg |
|---|---|
| Dimensions | 18.3 × 21 × 29.6 cm |
| Extended Product Type | E1.2N 250 Ekip Dip LSI 3p F F |
| Standard | IEC |
| Number of Poles | 3P |
| Execution Type | EL |
| Rated Current | 250A |
| Rated Voltage | 690V |
| Breaking Capacity | 66kA |
| Trip Unit | Ekip Dip LSI |
| Breaking Class | N |
| Rated Cross-Section | 12 cm² |
| Terminal type | Front |
| Product Net Depth (MM) | 18.3 cm |
| Customs Tariff Number | 85362090 |
| Minimum Order Quantity | 1 |
| GTIN (EAN) | 8.01564E+12 |
| L1 | Electrical |
| L2 | Switchgear & Contactors |
| L3 | Air Circuit Breakers |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Current Type | AC |
| Electrical Durability | Ue =< 440 V 8000 cycle |
| Extended Product Lifetime | Lifetime Extension Services are Offered |
| Mechanical Durability | 20000 cycle |
| Package Level 1 Depth / Length | 33 cm |
| Package Level 1 Gross Weight | 16 kg |
| Package Level 1 Height | 35 cm |
| Package Level 1 Width | 27 cm |
| Power Loss | 31 W |
| Product Name | Air Circuit Breaker |
| Rated Impulse Withstand Voltage (Uimp) | acc. to IEC 60947-2 12 kV |
| Rated Insulation Voltage (Ui) | AC 1000 V |
| Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics) | 100% |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 50 kA |
| Recommended Screw Driver | M12 |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops – Standard EN45555 – 77.6 % |
| Suitable for IT Networks | Yes, 690V |